Provided by PhD Pools, LPTICL 384 PROPERTY ADDRESS: 123
Lois Lane, The Woodlands, TX 77382
Inspection Fee: $150
paid in full at the time of the inspection.
INSPECTION DATE/TIME: 09/08/11 @ 10:00 a.m.
Weather Conditions: Sunny and Dry
VISUAL ASSESSMENT OF STRUCTURE:
1. INTERIOR FINISH…White plaster
is overall in good condition. There are some stains and hairline cracks. There was no
exposed gunite at the time of the inspection. Plaster is still serving its intended purpose which is to
make the structure water tight. All blemishes are cosmetic in nature and no need for replaster at this
time. The life expectancy for this type of plaster is 10 to 15 years with the proper care and maintenance.
2. Tile and grouting...good.
3. Coping…One
piece of flagstone is chipped.
4. Decking…Elevation of concrete is good. There is plenty of exposed foundation
on house and garage. There is no drainage to the street; however there is a deck-o-drain along the foundation
of the covered patio. Both sides of the drain are dammed up with landscaping and does not allow water to
exhaust out of drain. Recommend clearing both side of drain for better drainage.
5. Pool is level.
6. Elevation
of the pool is good. Pool has not settled.
MECHANICAL EQUIPMENT:
1.
Skimmers…The shallow end weir is sticking in the up position.
2. Main drain…dual drain system.
Drain covers are not VGB certified. This is only a recommendation not a code.
It is required for commercial pools and spas.
3. Returns…good.
4. Lights…There are two lights
in the pool and one in the spa. All lights are in good working order. The GFI works
and is located by the equipment and is working properly.
5. Water feature…Waterfall has a separate pump and is in good
working condition.
6. Pool Pump…Leak at suction and discharge side of pump. Needs repair.
7. Filter...PSI is
on the high end of normal when the cleaner valve is turned off. Recommend routine cleaning.
8. Heater…400,000
btu heater. Heater works.
9. Valves...Jandy valve for the 360 cleaner is leaking. Needs repair
a. Actuator valve for 360 is turned off and needs to be calibrated.
10. Chemical feeder...This
pool is equipped with a 320 inline chlorinator. Good condition.
a. This pool is also equipped with a Nature2 system. The cartridge is missing.
Recommend replacing.
11. Auto cleaning equipment...The hose on the cleaner needs to be cut to fit the pool.
It is too long and stays in a knot. Recommend new tail scrubber and wear ring on the tail.
There is a small leak at the energy filter. Recommend new o-ring. PSI gauge for
the energy filter sticks. Recommend replacing.
12. Equipment is bonded per code.
13. Gas meter...Good.
AC425
14. Equipment pad...good.
15. Fill line...none.
16. Fences and Gates...the
gates need to be self-closing and self-latching per code. Needs repair.
17. Overhead electrical
line...none.
18. Slide/diving board...none.
19. Spa…jets work well.
20. Time clocks and
controls…time clocks are working properly. Recommend labeling the outside controller and the four
function button at the spa.
21. Water was clear at the time of the inspection.
NOTICE: This is a report on
the condition of a swimming pool as inspected by the firm named below. The scope of the inspection was
limited to those aspects of the pool and related equipment, which were observable by visual external inspection from the ground
surface. No pressure tests were performed on the plumbing and none of the pool equipment components were
disassembled for purposes of this inspection. This report includes only those conditions, which were observable
after a reasonable examination of the pool in normal operating condition on the date of the inspection. The
inspection firm makes no representations as to existing conditions of the pool and related equipment other than as set forth
herein and observable by inspection in the manner set forth above.Allowances
will have been made if the pool is operational. The inspecting firm MAKES NO WARRANTIES, EXPRESS OR IMPLIED,
relating to the present condition of the pool and/or equipment nor suitability for continued service. Any party relying on
this report understands that the liability of the inspecting firm, arising from the inspection on which this report is based
shall be limited to the amount of the inspection fee paid. THIS IS NOT A CONTRACT OR A BID, BUT A FORM FOR INSPECTION ONLY. IF
ANY REPAIRS ARE NEEDED, OR IF WARRANTIES OR CONDITIONS OTHER THAN THAT STATED ABOVE ARE REQUIRED, A SEPARATE
CONTRACT PROPOSAL SHALL BE PROVIDED. THIS IS NOT A JUDGMENT AS TO COMPLIANCE WITH APSP STANDARDS.
INSPECTED BY: Lyle McManus, President of the General
Partners, CPOi
PhD Pools, LP 7 SWITCHBUD PLACE STE.
192C-421 THE WOODLANDS, TX 77380 281-825-1105